MetricsHub
MetricsHub Community Connectors 1.0.22
-
Home
- Connector Developer Guide Computes 24
perBitTranslation (Compute)
When To Use
Use perBitTranslation when a column contains a numeric status word in which each bit carries its own meaning (common in IPMI, Dell OpenManage, and other hardware instrumentation). The compute reads the value as an integer, tests every bit listed in bitList, looks up the key <bit>,1 when the bit is set (or <bit>,0 when it is clear) in the translation table, and replaces the cell with the non-empty matches joined by " - ".
Bits whose key is absent from the table, or translates to an empty string, contribute nothing; a value with no meaningful bits set becomes an empty cell.
Syntax
sources:
powerSupplies:
# DeviceID;StatusInformation
type: wmi
namespace: root\cimv2\dell
query: SELECT DeviceID, Status FROM CIM_PowerSupply
computes:
- type: perBitTranslation
column: 2
bitList: "0,2,3,6,7,8,9,10,11,12,13,14"
translationTable: ${translation::PowerSupplyStatusInformationTranslationTable}
# Translation tables are declared in the top-level `translations:` section
translations:
PowerSupplyStatusInformationTranslationTable:
"0,1": ""
"2,1": Not Ready
"3,1": Fan Failure
"6,1": AC Switch On
"7,1": AC Power On
"9,1": Failed
"10,1": Predicted Failure
"11,1": AC Lost
"12,1": AC Lost or Out-of-range
"13,1": AC Out-of-range
"14,1": Configuration Error
Properties
| Property | Required | Default | Description |
|---|---|---|---|
type |
Yes | None | perBitTranslation. |
column |
Yes | None | 1-based index of the column holding the numeric value to decode. The value must parse as a number (a decimal form such as 520.0 left by an earlier arithmetic compute is accepted). |
bitList |
Yes | None | Comma-separated list of bit positions to test, e.g. "0,2,3,6". Bit 0 is the least-significant bit. Bits are evaluated in bitList order. |
translationTable |
Yes | None | Reference to a table declared under the top-level translations: section, written ${translation::TableName}. Keys have the form "<bit>,1" (bit set) or "<bit>,0" (bit clear). Unlike translate and arrayTranslate, the default key is not used by this compute. |
Table Transformation Example
With the table above, 520 = bits 3 and 9 set, and 192 = bits 6 and 7 set:
Input
| DeviceID | Status |
|---|---|
| PS1 | 520 |
| PS2 | 192 |
Result
| DeviceID | StatusInformation |
|---|---|
| PS1 | Fan Failure - Failed |
| PS2 | AC Switch On - AC Power On |
Recommended Pattern
- List in
bitListonly the bits that carry meaning for the monitor; unlisted bits are ignored. - Use
"<bit>,0"entries when the absence of a bit is the noteworthy condition (e.g."7,0": AC Power Off). - If the device reports the status word in hexadecimal, insert a
convert[1] compute withconversion: hex2Decfirst. - Duplicate the column upstream (
duplicateColumn) when you also need the raw value or a separatetranslateof the same word.
Common Mistakes
- Treating the cell as a binary string: the engine parses it as an integer and tests powers of two, so
"101"means one-hundred-one, not bits 0 and 2. - A non-numeric value in the column aborts the compute for the whole table, leaving every row untranslated.
- Forgetting to quote the table keys:
"13,1": AC Out-of-rangemust be a quoted string key. - Expecting a
defaultfallback — this compute ignores thedefaultentry; unmatched bits are simply skipped.
Community Examples
No community connector currently uses perBitTranslation; the examples above are illustrative, adapted from enterprise-grade connectors such as Dell OpenManage.