IPMI Java Client 2.0.00
-
Home
- Usage
Chassis Status
The IPMI Get Chassis Status command reports whether the server is powered on, why it last changed power state, what it does when mains power returns, and a few fault and front panel flags. It is a single request: reading it is fast, and it is a good way to check that the credentials work.
The ChassisStatus object
try (IpmiClient bmc = IpmiClient.builder(host).credentials(user, password).build()) {
ChassisStatus status = bmc.chassisStatus();
System.out.println("Power: " + (status.powerOn() ? "on" : "off"));
System.out.println("Restore policy: " + status.powerRestorePolicy());
System.out.println("Intrusion: " + status.intrusion());
}
ChassisStatus[1] decodes the response (IPMI 2.0, section 28.2) and never throws:
| Method | Meaning |
|---|---|
powerOn() |
System power is on |
powerRestorePolicy() |
What happens when mains power returns: PoweredOff, PowerRestored (back to the previous state), PoweredUp, or Unknown when the BMC reports it as such |
lastPowerEvents() |
Why the system last changed power state, as a set of PowerEvent[2]: AC_FAILED, POWER_OVERLOAD, INTERLOCK, POWER_FAULT, IPMI_COMMAND; several can be flagged at once |
powerFault() |
A fault was detected in the main power subsystem |
powerOverload() |
The system was shut down because of a power overload |
interlock() |
A power interlock (a switch that cuts power when the chassis is open) is active |
powerControlFault() |
The power controller tried to change the power state and failed |
coolingFault() |
A cooling or fan fault was detected |
driveFault() |
A drive fault was detected |
intrusion() |
The chassis intrusion sensor is active (the case is or was open) |
frontPanelLockout() |
The power off and reset buttons of the front panel are disabled |
identifyState() |
The state of the identify LED (Off, TemporaryOn, IndefiniteOn), or empty when the BMC does not report it |
data() |
The raw GetChassisStatusResponseData[3], for the front panel button flags and the raw bytes |
Not every BMC fills every flag: the intrusion, drive and cooling bits in particular are optional in the specification, and a BMC that does not implement them reports false.
Controlling the power
chassisControl(PowerCommand) sends the Chassis Control command (IPMI 2.0, section 28.3). It needs a client built with the Operator or Administrator privilege[4], which the client requests at login and sets right after it (Set Session Privilege Level): at the default User level the BMC refuses the command with D4h, and an account not allowed Operator fails the first operation with IpmiAuthenticationException.
try (IpmiClient bmc = IpmiClient.builder(host).credentials(user, password)
.privilege(PrivilegeLevel.Operator).build()) {
if (!bmc.chassisStatus().powerOn()) {
bmc.chassisControl(PowerCommand.PowerUp);
}
}
PowerCommand |
Effect |
|---|---|
PowerUp |
Power the system on |
PowerDown |
Power it off at once (soft off, S4/S5), without shutting the operating system down |
PowerCycle |
Power it off for at least a second, then on. Optional: a BMC should refuse it with D5h when the system is off, but some power the system on instead, so check powerOn() first |
HardReset |
Pulse the reset signal. A BMC that can tell it would do nothing (the system is off) should refuse it with D5h |
SoftShutdown |
Ask the operating system to shut down through ACPI, by emulating a fatal overtemperature (optional) |
DiagnosticInterrupt |
Pulse a diagnostic interrupt, an NMI on x86, so that the operating system writes a diagnostic dump (optional) |
The BMC answers as soon as it accepts the command, and carries it out afterwards: a power off takes a few seconds, a soft shutdown as long as the operating system needs. Poll chassisStatus().powerOn() to see the state change. A refused command fails with IpmiCompletionCodeException[5]: D4h at a session below Operator, D5h for a command the system's present state does not allow, CCh for an optional command the BMC does not implement.
Unlike the read operations, a control command is sent once: not again when its reply is lost or is a C3h (a timeout on the BMC side, which says the response is unavailable, not that nothing was done), since the BMC may have carried it out and a second reset would reset the system twice, and not on a new session. A lost reply fails with IpmiTimeoutException, a C3h with IpmiCompletionCodeException, and chassisStatus() then tells what the BMC did; a busy BMC (C0h), which did nothing, is retried as for any command. PowerCycle is refused with IllegalStateException, before anything is sent, when the system is off: the specification recommends that check, as some BMCs power the system up instead of doing nothing.
The identify LED
chassisIdentify(int seconds) sends the Chassis Identify command (IPMI 2.0, section 28.5): the chassis identifies itself, typically by blinking a LED, for the given number of seconds (1 to 255; the BMC may stretch it by 20%). chassisIdentify(0) turns the identify off, and chassisIdentifyForever() keeps it on until then, with the optional “force identify on” byte of the command, which not every BMC implements (CCh from those that do not). Both need the Operator privilege, are sent once like the power commands, and identifyState() of the chassis status reports the result on the BMCs that support it:
bmc.chassisIdentify(30);
System.out.println(bmc.chassisStatus().identifyState()); // Optional[TemporaryOn]
bmc.chassisIdentify(0);